| size | ampacity | OCPD | EGC | drop V | drop % | |
Ampacities: NEC 310.16, 75 °C Cu, 30 °C ambient, up to 3 current-carrying conductors — derate for more. Small-conductor OCPD caps per 240.4(D): 14→15 A · 12→20 A · 10→30 A. Effective Z from Ch.9 Table 9 (Cu, PVC conduit, 0.85 PF). EGC per 250.122.
above 600 V — MV quick reference
5 kV class → 2.4 / 4.16 kV systems · 8 kV → 7.2 kV · 15 kV → 13.2 / 13.8 / 14.4 kV · 25 kV → 24.94 kV · 35 kV → 34.5 kV (L-L)
Typical: EPR/XLPE insulation, 133%/100% insulation level, copper, shielded, in concrete-encased duct or direct burial (jacketed). Terminations: load-break elbows (deadfront) or potheads — only with proper MV training/PPE. Min bending radius ≈ 8–12× D. Sizing must follow the manufacturer's ampacity table (duct bank grouping, soil RHO, loading depth) — never a web tool alone.